Switch to mobile site
Loading

Gas Safety

Exam revision materials for Plumbing Level 2&3 and ACS Gas Safety test

Create an Article

Gas Pipework

New Installation

Click to show/hide index

Regulations

Acts

Code of Practice

Guidance

Standards

Gas Supply

Gas Meters

Safety Devices and Controls

Air/Gas ratio valves

Appliances Controls

Flame Supervision Devices FSD

Gas Controls

Gas Meter Controls

Safety Cut-off Devices

Spare Part Identification

Pipework

Open-vented System

Ventilation

Gas Appliances

Ventilation Sizing

Unsafe Situations

Dealing with Unsafe Situations

Emergency Notices and Warning Labels

Gas Leak

Regulations

Commissioning

Purging

Tightness Test

Gas Performance

Gas Rate

Heat Input

Gas Pipework

Gas Fittings and Pipes

Gas Supply

Materials

New Installation

Pipe Protection

Pipework Sizing

Chimney and Flue

Chimneys

Flue Construction

Flue Inspection and Testing

Flue Terminals

Flue Types

Combustion

Carbon Monoxide Poisoning

Combustion Process

Natural Gas

Portable Combustion Gas Flue Analysers

Boilers

Components and Safety Devices

Gas Installation Types

  • low-pressure installation (up to 350mbar)
  • medium pressure-fed installation (up to 8.6bar)
< Go Back2013-03-16

Underfloor installation

  • 150mm away from electrical meters
  • 25mm away from any electricity supply cables or metallic services
  • BS 6891 - protected against damage and corrosion
  • Notching:
    Notching
    • MAX depth is D/8
    • S/14<Position from the wall<S/4
  • Drilling:
    Drilling
    • MIN distance apart = 3Ø
    • S/4<Position from the wall<2/5S
    • MAX diameter = D/4
  • Chasing:
    • horizontal = T/6
    • vertical = T/3
< Go Back2013-03-16

Equipotential Bonding

  • MAX within 600mm of the meter
  • 10mm2 minimum cable size
  • 1200mm - minimum length
< Go Back2013-03-16

Exterior Pipework

Exterior gas pipework
  • External control valve where the gas pipe leaves the dwelling
  • MIN 375mm depth for buried pipework in driveways, open soil , lawns or gravel paths
  • MIN 40mm depth for buried pipework under pedestrian concrete path
< Go Back2013-03-16