Electronic Gas Flue Analyser
- Should confirm to BS EN 50379-3 (BS7927:1998)
- Should measure:
- O2 oxygen
- CO carbon monoxide in parts per million (ppm)
- CO2 carbon dioxide
- CO/CO2 ratio
- Temperature
- NO Nitrogen monoxide
- Pressure
- Excess air
- Combustion efficiency
- Most analysers do not measure the absolute levels of CO and O2
- Analysers are not designed for continuous measurement
- Should not be used to identify leakage of combustion products
- Not all analysers can record the maximum CO reading
- Accuracy
- Readings at or below 20ppm - ±3ppm
- Readings above 20ppm - ±5%
< Go Back | 2013-03-12 |
Gas Analyser Preparation and Use
- A small bottle of calibration gas can be used to check the sensor
- Analyser reading can be affected by:
- cooking activities
- cleaning fluids
- polishes and paints
- Multi-hole sample probe for use on gas cookers
- "Zero" procedure - O2 reading in outdoor air is 20.9%
- Do not smoke before or during the test
- Preparation for testing:
- Position sampling probe 2m above the floor level and 1m away from appliances
- Record the level of CO over 15min period
- there shouldn't be any rise of CO level
- Testing
- With only one appliance on measure the CO level
- If at any time the CO reading exceeds 30ppm (except when testing cookers):
- stop the test
- turn off all appliances
- open all windows and doors to ventilate the room
- and vacate the room under test
- Flueless Cookers Testing
- Ensure that ventilation is unobstructed
- Put 2 saucepan (with 1 liter of water; 160 to 220mm base) on 2 largest pan-supports
- Place the grill pan in its highest position under the grill
- Light the grill, oven (at mid-range) and 2 hotplate burners at maximum
- Turn hotplates down to simmer when water boils
- Turn the grill off after 30min
- Record CO levels at 1min intervals:
- Reading doesn't exceed 30ppm - pass
- Reading doesn't exceed 30ppm for 20min and falling not exceeding 90ppm - pass
- Reading exceeds 90ppm - fail
- Flueless Water Heaters
- Light the appliance at maximum rate for 5 minutes recording the CO levels at 1 min intervals
- Flueless Space Heaters
- Light the appliance at maximum rate for 30 minutes recording the CO levels at 1 min intervals
< Go Back | 2013-03-12 |
Combustion Performance (CO/CO2 ratio) Action Levels
Appliance type | CO/CO2 ratio | |
---|---|---|
Back boiler unit | Boiler unit | 0.008 |
In combination with fire | 0.020 | |
Central heating boiler | 0.008 | |
Circulator | 0.010 | |
Flued space heater | Fire Convector Heater | 0.020 |
Flueless space heater | Fire Convector Heater | 0.001 |
Flueless cabinet heater (LPG) | 0.004 | |
Water heater - flued and flueless | 0.020 | |
Warm air heater | 0.008 | |
Flueless cookers | Cooker oven | 0.008 |
Cooker hob | Assess flame picture | |
Cooker grill (CE marked) | 0.010 | |
Cooker grill (non CE marked) | 0.020 | |
Range oven (flued) | 0.020 | |
Refrigerator (LPG) | 0.007 | |
Tumble drier | Flued | 0.010 |
Flueless | 0.001 | |
Gas lights (LPG) | 0.020 |
< Go Back | 2013-03-12 |