F&E Tank or Feed and Expansion Cistern

  • Water Level :
    • MUST be set to allow 4% expansions of the water in the system
    • SHOULD be set just above the cold feed to heating system
    • MUST be below that of the CWSC to prevent contamination
  • 18L – common size of F&E for domestic
  • MIN height of F&E - pump head divided by 3 (to avoid problems with gravity primaries)
< Go Back2013-04-19

Open Vent Pipe

    • MIN size is 22mm
    • Primary open vent rises for 450mm above the cistern – preventing surge effect
       primary vent pipe hight
    • No valves on the pipe
< Go Back2013-04-19

Air Separator

    • causes turbulence that separates the dissolved oxygen

Air Separator Installation Details

< Go Back2013-04-19